CREIA - California Real Estate Inspection Association

You are here: Home April 2010 eNews August 2009 Inspector eNews

August 2009 Inspector eNews

E-mail Print PDF
Article Index
August 2009 Inspector eNews
Page 2
Page 3
Page 4
All Pages
The CREIA Inspector eNewsThe CREIA Inspector eNewsThe CREIA Inspector eNews
August 2009 | Archives

Insurance Matters — The Elevator and the Death of a Child

An analysis by Michael Casey of Casey, O’Malley Associates and Robert Pearson of the Allen Insurance Group

An Inspector performed an inspection on a home that contained an elevator.

In his report under the “Doors/Stairs” section the inspector wrote “Consult contractor regarding remodel/installation of stair and removal of elevator. Elevator appears functioning and satisfactory at time of inspection”.  Under the “Walls” section of the report he wrote “Wall structure not plumb in elevator area, structure appears modified.  Consult contractor regarding repair/remodel/installation of stairs between levels and returning the laundry/bathroom to original layout”.  In both sections he marked “Consult specialist”.

The elevator was made of plywood and did not have doors.  It was installed by the sellers – with no permit.

Allen Insurance "The" Source for Home Inspector Insurance Since 1992

A short time after the buyer (a single parent) moved in, her 8 year old son was pinned between the floor and heating duct work as the elevator was moving. The child died in his mother’s arms after she had freed him.

We are not aware of any standards that require any inspection of an elevator what so ever.  Most standards exclude any requirement to report on any system or component not specifically addressed in the standards.

By mentioning that the elevator was functional at the time of the inspection we lost all ability to defend the claim.  It did not matter that he recommended removal of the elevator – particularly in the case of a child’s death.

The inspector’s insurance company spent $100,000 in defense expenses and finally settled the matter for $140,000.

It is unusual to have an elevator in a home and the following comment could have been used to protect the inspector.  Also in this particular situation the elevator installation had affected the integrity of the structure so a comment was necessary regarding that situation.

“The home has an elevator. Elevators are unique systems and are outside the scope of our standards of practice and it was not inspected. We are not qualified to inspect elevators and recommend you have a qualified specialist contractor inspect the elevator prior to settlement/close of escrow”.

In closing, normally we recommend being silent on systems and components that are not required to be inspected by the standards of practice you reference.   However, when you have a potentially life threatening situation, it is our recommendation you use comments like the preceding to protect yourself and put your client on notice to have the system evaluated – even if they chose to not do so.

Bob Pearson is the Executive Director/Vice President of the Allen Insurance Group. He began his career in home inspections in 1985 and has had three inspection businesses. He has performed thousands of inspections, with an emphasis on commercial properties. In 1992 he was employed by the Allen Insurance Group to create their home inspectors program. He is a member of many inspector associations and is widely recognized as an expert on home inspector insurance.


Click here to learn about OREP Home Inspector E&O Insusrance


Take Your Business to the Next Level! Call TWI Affiliates Training


COA - Casey, O'Malley Associates - The Right Direction


This Issue ...

Affiliate Spotlight - Home Inspection Reporting System

Ethics - Find a Hurt and Be a Solution

Technical Article - Foundation Framing Connections

InspecTest

Off the Net

July 2009 BOD Synopsis (Members Only)

Membership Survey Results Summary (Members Only)

CREIA July 2009 Leadership Day and BOD Meetings Photos

$25 Link Fee

CREIA's Online Calendar

Upcoming CREIA Events
 

New Deck Codes – A Seminar to benefit CCHI

Approved for 4 CECs
When: Tuesday, Aug 11, 2009
Where: 1425 Moonstone, Brea, CA 92821
Time: 7:30 am (Check-in) Seminar: 8:00 am – 12:00 noon
Description: New Deck Codes
Price: $40 - Includes new Simpson catalogue


New Deck Codes – A Seminar to benefit CCHI

Approved for 4 CECs
When: Wednesday, Sep 30, 2009
Where: 5151 S. Airport Way, Stockton, CA 95206
Time: 7:30 am (Check-in) Seminar: 8:00 am – 12:00 noon
Description: New Deck Codes
Price: $40 - Includes new Simpson catalogue


Electrical Seminar with Douglas Hansen

Approved for 8 CECs
When: Friday, October 23, 2009
Where: Vina Robles Winery & Hospitality Center
 3700 Mill Road, Paso Robles, CA 93446
 (805) 227-4812
Time: 7:30 am (Check-in) Seminar: 8:00 am – 5:00 pm
Price: $159 includes lunch & CodeCheck California handout

Register soon!


QUESTIONS?
Contact:   CREIA Meetings
meetings@creia.org
800/848-7342

 


1 | 2 | 3 | 4 »

Page 1



EVENTS &
EDUCATION

Click here to go to the CREIA Meeting and Events Calendar


Congratulations!

New Candidates

Paula Martin
Lane Aebi
Rick Dehlinger
Stephen Miller
Paul Stream
David Davis
Gary Gramling
Mike Grafton

New CCIs

Brian Dwight


Visit Ask.CREIA.org


 

 
The CREIA Inspector eNewsThe CREIA Inspector eNewsThe CREIA Inspector eNews
August 2009 | Archives

Insurance Matters — The Elevator and the Death of a Child

An analysis by Michael Casey of Casey, O’Malley Associates and Robert Pearson of the Allen Insurance Group

An Inspector performed an inspection on a home that contained an elevator.

In his report under the “Doors/Stairs” section the inspector wrote “Consult contractor regarding remodel/installation of stair and removal of elevator. Elevator appears functioning and satisfactory at time of inspection”.  Under the “Walls” section of the report he wrote “Wall structure not plumb in elevator area, structure appears modified.  Consult contractor regarding repair/remodel/installation of stairs between levels and returning the laundry/bathroom to original layout”.  In both sections he marked “Consult specialist”.

The elevator was made of plywood and did not have doors.  It was installed by the sellers – with no permit.

Allen Insurance "The" Source for Home Inspector Insurance Since 1992

A short time after the buyer (a single parent) moved in, her 8 year old son was pinned between the floor and heating duct work as the elevator was moving. The child died in his mother’s arms after she had freed him.

We are not aware of any standards that require any inspection of an elevator what so ever.  Most standards exclude any requirement to report on any system or component not specifically addressed in the standards.

By mentioning that the elevator was functional at the time of the inspection we lost all ability to defend the claim.  It did not matter that he recommended removal of the elevator – particularly in the case of a child’s death.

The inspector’s insurance company spent $100,000 in defense expenses and finally settled the matter for $140,000.

It is unusual to have an elevator in a home and the following comment could have been used to protect the inspector.  Also in this particular situation the elevator installation had affected the integrity of the structure so a comment was necessary regarding that situation.

“The home has an elevator. Elevators are unique systems and are outside the scope of our standards of practice and it was not inspected. We are not qualified to inspect elevators and recommend you have a qualified specialist contractor inspect the elevator prior to settlement/close of escrow”.

In closing, normally we recommend being silent on systems and components that are not required to be inspected by the standards of practice you reference.   However, when you have a potentially life threatening situation, it is our recommendation you use comments like the preceding to protect yourself and put your client on notice to have the system evaluated – even if they chose to not do so.

Bob Pearson is the Executive Director/Vice President of the Allen Insurance Group. He began his career in home inspections in 1985 and has had three inspection businesses. He has performed thousands of inspections, with an emphasis on commercial properties. In 1992 he was employed by the Allen Insurance Group to create their home inspectors program. He is a member of many inspector associations and is widely recognized as an expert on home inspector insurance.


Click here to learn about OREP Home Inspector E&O Insusrance


Take Your Business to the Next Level! Call TWI Affiliates Training


COA - Casey, O'Malley Associates - The Right Direction


This Issue ...

Affiliate Spotlight - Home Inspection Reporting System

Ethics - Find a Hurt and Be a Solution

Technical Article - Foundation Framing Connections

InspecTest

Off the Net

July 2009 BOD Synopsis (Members Only)

Membership Survey Results Summary (Members Only)

CREIA July 2009 Leadership Day and BOD Meetings Photos

$25 Link Fee

CREIA's Online Calendar

Upcoming CREIA Events
 

New Deck Codes – A Seminar to benefit CCHI

Approved for 4 CECs
When: Tuesday, Aug 11, 2009
Where: 1425 Moonstone, Brea, CA 92821
Time: 7:30 am (Check-in) Seminar: 8:00 am – 12:00 noon
Description: New Deck Codes
Price: $40 - Includes new Simpson catalogue


New Deck Codes – A Seminar to benefit CCHI

Approved for 4 CECs
When: Wednesday, Sep 30, 2009
Where: 5151 S. Airport Way, Stockton, CA 95206
Time: 7:30 am (Check-in) Seminar: 8:00 am – 12:00 noon
Description: New Deck Codes
Price: $40 - Includes new Simpson catalogue


Electrical Seminar with Douglas Hansen

Approved for 8 CECs
When: Friday, October 23, 2009
Where: Vina Robles Winery & Hospitality Center
 3700 Mill Road, Paso Robles, CA 93446
 (805) 227-4812
Time: 7:30 am (Check-in) Seminar: 8:00 am – 5:00 pm
Price: $159 includes lunch & CodeCheck California handout

Register soon!


QUESTIONS?
Contact:   CREIA Meetings
meetings@creia.org
800/848-7342

 


1 | 2 | 3 | 4 »

Page 1



EVENTS &
EDUCATION

Click here to go to the CREIA Meeting and Events Calendar


Congratulations!

New Candidates

Paula Martin
Lane Aebi
Rick Dehlinger
Stephen Miller
Paul Stream
David Davis
Gary Gramling
Mike Grafton

New CCIs

Brian Dwight


Visit Ask.CREIA.org


 

 
>
The CREIA Inspector eNewsThe CREIA Inspector eNewsThe CREIA Inspector eNews
August 2009 | Archives

Page « 1 | 2 | 3 | 4 »


Affiliate Spotlight:
Home Inspection Reporting System - Reporting Software That Includes Online Report Hosting And Storage.

Horizon by Carson Dunlop is a complete home inspection business and reporting system developed by the most respected name in professional home inspection: Carson, Dunlop & Associates. With more than 30 years experience as industry leaders, we know what it takes to operate a successful business and effectively work with customers before, during and after an inspection. We’ve combined these tools into one system, Horizon, created by home inspectors, for home inspectors.

Carson Dunlop has been devoted to building inspection since 1978. Inspector training and resources include The Home Study System, ASHI@Home, The Illustrated Home and The Home Reference Book. Carson Dunlop continues to lead in innovation with Horizon Home Inspection Reporting software.

Horizon is a perfect solution for inspectors who need an affordable package to write reports on Laptop or Tablet computers, or on PocketPCs, online or offline.  Horizon provides the flexibility to work at the office or onsite.  Horizon helps to shorten the report writing process without sacrificing the very high quality finished product. Horizon is user-friendly, getting you up to speed in no time.  Horizon includes business tools that track, manage and report on your business success.

“The price is so compelling” and it includes free set-up, free scheduling and work order functions, free report hosting and archiving (photos too!), free support, and free updates! – J.Kwasnik

Key Features:

  • Graphic Scheduler & Work Order Manager – easy for you or your staff to book anywhere you have internet access.
    • Invoicing – Effortless receivables management.
    • Confirmation email can include electronic contract for instant client acceptance.
    • Yahoo Maps integrated to track your location.
    • Agent statistics – track your referrals!
  • Move easily through the report – add items and your notes.
    • Build your own comment library – say it once and use it over again.
    • Add / Edit photos – Simple. Fast. Easy.
    • Create report templates for lists of common items.
    • > 250 Title page designs
  • Library of color illustrations and technical information are added automatically – help to educate your readers.

Horizon makes a good inspector look great!  Get up and running for $240. For more information about Horizon, or to schedule a demonstration, please email John Kwasnik or call 800-268-7070.


Allen Insurance "The" Source for Home Inspector Insurance Since 1992


Click here to learn about OREP Home Inspector E&O Insusrance


Take Your Business to the Next Level! Call TWI Affiliates Training


COA - Casey, O'Malley Associates - The Right Direction


Ethics - Find a Hurt and Be a Solution

My mentor, for inspection matters, lives in community outside of Denver. When I visit Colorado, particularly the higher elevations, he encourages me to make sure I arrive a day or so before any scheduled events to become acclimated to the elevation. Several years ago I attended an inspector conference he had put together in Breckenridge, Colorado. Breckenridge sits just a few feet below outer space in terms of elevation. I soon realized there are places in Colorado where, like Breckenridge, they forgot to put oxygen in the air. I returned to Colorado a few days ago to attend to a church related conference, with my mentor friend, at the University of Colorado in Boulder. He assured me there was oxygen in the air in Boulder. The weather was perfect, but I found the air to be a little too clean for my California constitution. I’ve always felt you need a few impurities in the air to ward off sickness. On the positive side I think the clean air gave rise to clear thinking. That is a rare event in my case. The conference did not shed any new light on how to inspect a garage or safely climb a ladder. However, regardless of what kind of conference I attend, I always find little nuggets of truth that I can use to make improvements to myself, my marriage and my business relationships.

The CREIA web site states that the “Code of Ethics establishes guidelines for our interactions with our clients, sellers, and agents. These guidelines foster a higher level of public trust of our profession and organization as clients and agents learn they can depend on our clear, ethical behavior. We agree to abide by the Code as a condition of CREIA membership. Adherence to the ethical guidelines is critical in promoting our credibility as individuals and as an organization.” Over the last months there has been an increase of phone calls, emails as well as ethics complaints which center on the business relationships. As I look at these communications, I see a common thread. The real estate community is hurting. Financially, emotionally, physically they are hurting.

One of the speakers at the Boulder conference was the former head football coach at the University of Colorado. He spoke specifically about the responsibility that churches, of all flavors, have in helping the homeless, poor, widows, orphans, the unemployed, etc. Without going into the specifics of his presentation, he gave me one of those transferable nuggets that I can use in my business relationships. Churches lose creditability and influence when they are not out meeting the needs of the community. He essentially said, find a hurt in the community and be a solution to the hurt. There are certainly many in the real estate community who are hurting. What’s the nugget? CREIA is uniquely situated in the struggling real estate community to be a source of encouragement. I am swift to get on the phone with a Realtor® and ask for an inspection, I must admit it's been a long time since I’ve gotten on the phone with a Realtor® to ask them how they are doing and provide a word of encouragement. I spend a lot of time being frustrated with title companies who are late in sending my escrow check. I can’t remember the last time, if ever, I called a title company to encourage them, rather than “rag” on them. Eighty percent of the students in my daughter’s surgical technology class are unemployed mortgage brokers who are scrambling to find another career. We all know many inspectors who have retired their flashlights and are out looking for other work. I would encourage CREIA members to block out just 15 minutes a week and spend that time providing encouragement to those in the real estate community. Why should we do it? Not because it would increase our business, even though it probably would, but because it’s the right thing to do. Providing random acts of kindness and compassion is not a new idea but maybe for the inspection industry, it’s an idea whose time has come. When the real estate community thinks of CREIA I would hope they see us as a breath of fresh air.

Submitted byDavid Pace, CREIA MCI, Ethics Chair


« 1 | 2 | 3 | 4 »

Page 2



EVENTS &
EDUCATION

Click here to go to the CREIA Meeting and Events Calendar


Congratulations!

New Candidates

Paula Martin
Lane Aebi
Rick Dehlinger
Stephen Miller
Paul Stream
David Davis
Gary Gramling
Mike Grafton

New CCIs

Brian Dwight


Visit Ask.CREIA.org


 

 
The CREIA Inspector eNewsThe CREIA Inspector eNewsThe CREIA Inspector eNews
August 2009 | Archives

Page « 1 | 2 | 3 | 4 »


Affiliate Spotlight:
Home Inspection Reporting System - Reporting Software That Includes Online Report Hosting And Storage.

Horizon by Carson Dunlop is a complete home inspection business and reporting system developed by the most respected name in professional home inspection: Carson, Dunlop & Associates. With more than 30 years experience as industry leaders, we know what it takes to operate a successful business and effectively work with customers before, during and after an inspection. We’ve combined these tools into one system, Horizon, created by home inspectors, for home inspectors.

Carson Dunlop has been devoted to building inspection since 1978. Inspector training and resources include The Home Study System, ASHI@Home, The Illustrated Home and The Home Reference Book. Carson Dunlop continues to lead in innovation with Horizon Home Inspection Reporting software.

Horizon is a perfect solution for inspectors who need an affordable package to write reports on Laptop or Tablet computers, or on PocketPCs, online or offline.  Horizon provides the flexibility to work at the office or onsite.  Horizon helps to shorten the report writing process without sacrificing the very high quality finished product. Horizon is user-friendly, getting you up to speed in no time.  Horizon includes business tools that track, manage and report on your business success.

“The price is so compelling” and it includes free set-up, free scheduling and work order functions, free report hosting and archiving (photos too!), free support, and free updates! – J.Kwasnik

Key Features:

  • Graphic Scheduler & Work Order Manager – easy for you or your staff to book anywhere you have internet access.
    • Invoicing – Effortless receivables management.
    • Confirmation email can include electronic contract for instant client acceptance.
    • Yahoo Maps integrated to track your location.
    • Agent statistics – track your referrals!
  • Move easily through the report – add items and your notes.
    • Build your own comment library – say it once and use it over again.
    • Add / Edit photos – Simple. Fast. Easy.
    • Create report templates for lists of common items.
    • > 250 Title page designs
  • Library of color illustrations and technical information are added automatically – help to educate your readers.

Horizon makes a good inspector look great!  Get up and running for $240. For more information about Horizon, or to schedule a demonstration, please email John Kwasnik or call 800-268-7070.


Allen Insurance "The" Source for Home Inspector Insurance Since 1992


Click here to learn about OREP Home Inspector E&O Insusrance


Take Your Business to the Next Level! Call TWI Affiliates Training


COA - Casey, O'Malley Associates - The Right Direction


Ethics - Find a Hurt and Be a Solution

My mentor, for inspection matters, lives in community outside of Denver. When I visit Colorado, particularly the higher elevations, he encourages me to make sure I arrive a day or so before any scheduled events to become acclimated to the elevation. Several years ago I attended an inspector conference he had put together in Breckenridge, Colorado. Breckenridge sits just a few feet below outer space in terms of elevation. I soon realized there are places in Colorado where, like Breckenridge, they forgot to put oxygen in the air. I returned to Colorado a few days ago to attend to a church related conference, with my mentor friend, at the University of Colorado in Boulder. He assured me there was oxygen in the air in Boulder. The weather was perfect, but I found the air to be a little too clean for my California constitution. I’ve always felt you need a few impurities in the air to ward off sickness. On the positive side I think the clean air gave rise to clear thinking. That is a rare event in my case. The conference did not shed any new light on how to inspect a garage or safely climb a ladder. However, regardless of what kind of conference I attend, I always find little nuggets of truth that I can use to make improvements to myself, my marriage and my business relationships.

The CREIA web site states that the “Code of Ethics establishes guidelines for our interactions with our clients, sellers, and agents. These guidelines foster a higher level of public trust of our profession and organization as clients and agents learn they can depend on our clear, ethical behavior. We agree to abide by the Code as a condition of CREIA membership. Adherence to the ethical guidelines is critical in promoting our credibility as individuals and as an organization.” Over the last months there has been an increase of phone calls, emails as well as ethics complaints which center on the business relationships. As I look at these communications, I see a common thread. The real estate community is hurting. Financially, emotionally, physically they are hurting.

One of the speakers at the Boulder conference was the former head football coach at the University of Colorado. He spoke specifically about the responsibility that churches, of all flavors, have in helping the homeless, poor, widows, orphans, the unemployed, etc. Without going into the specifics of his presentation, he gave me one of those transferable nuggets that I can use in my business relationships. Churches lose creditability and influence when they are not out meeting the needs of the community. He essentially said, find a hurt in the community and be a solution to the hurt. There are certainly many in the real estate community who are hurting. What’s the nugget? CREIA is uniquely situated in the struggling real estate community to be a source of encouragement. I am swift to get on the phone with a Realtor® and ask for an inspection, I must admit it's been a long time since I’ve gotten on the phone with a Realtor® to ask them how they are doing and provide a word of encouragement. I spend a lot of time being frustrated with title companies who are late in sending my escrow check. I can’t remember the last time, if ever, I called a title company to encourage them, rather than “rag” on them. Eighty percent of the students in my daughter’s surgical technology class are unemployed mortgage brokers who are scrambling to find another career. We all know many inspectors who have retired their flashlights and are out looking for other work. I would encourage CREIA members to block out just 15 minutes a week and spend that time providing encouragement to those in the real estate community. Why should we do it? Not because it would increase our business, even though it probably would, but because it’s the right thing to do. Providing random acts of kindness and compassion is not a new idea but maybe for the inspection industry, it’s an idea whose time has come. When the real estate community thinks of CREIA I would hope they see us as a breath of fresh air.

Submitted byDavid Pace, CREIA MCI, Ethics Chair


« 1 | 2 | 3 | 4 »

Page 2



EVENTS &
EDUCATION

Click here to go to the CREIA Meeting and Events Calendar


Congratulations!

New Candidates

Paula Martin
Lane Aebi
Rick Dehlinger
Stephen Miller
Paul Stream
David Davis
Gary Gramling
Mike Grafton

New CCIs

Brian Dwight


Visit Ask.CREIA.org


 

 
>
The CREIA Inspector eNewsThe CREIA Inspector eNewsThe CREIA Inspector eNews
August 2009 | Archives

Page « 1 | 2 | 3 | 4 »


Technical Article
Foundation Framing Connections

Proper connections between the framing of a dwelling and the foundation system are critical.  These connections provide the path to transfer building live and dead loads down through the structure to the foundation system where it is dispersed into the soil.  The further down the load path you go – the higher the stress on the connections.  Baring wood decay or other issues, wood-framing members themselves rarely fail.  It is the connections that fail when exposed to high stress conditions.  In California, we generally call those “earthquakes.”

Framing Connections Are Critical
Most of California falls into Seismic Design Category D.  A small part of California in the central valley/Modesto area falls into Seismic Design Category C.  For Seismic Design Categories D & E, the CBC 2007 requires that positive connections and anchorage be installed between the foundation and the framing system.  The installed connections must be sufficient to resist the design loads.  When earthquake lateral design forces exceed 150 pounds per foot, the toenail capacity is not taken into account in the load calculations.  In that case, additional means must be provided to insure proper load transfer.  This would generally be some sort of structural metal connector, etc.

Where the framing members are not continuous from foundation sill to roof, the members must be properly secured to insure a continuous load path.  Metal fasteners or straps may be required to be installed to insure a continuous load path.

At the bottom of a braced or shear wall, the attachment of the plate and the floor decking to the floor framing provides the load and shear transfer from the wall and the floor diaphragm to the floor framing below.  When nails or lag screws resist shear, they must be sufficiently long enough to penetrate through the sole plate and floor sheathing into the framing member below.

The fastening requirements for wood framed construction are found in CBC 2007 Table 2304.9.1.  For full load values, the CBC specifies a minimum fastener penetration into the framing member.  When the minimum fastener penetration falls below the values specified in the relevant table, the fastener cannot be taken into consideration when calculating the load capacity of the system.

The CBC requires that all wood studs have full bearing on the sill or plate.  While notching a stud over a foundation bolt is a common practice, it is improper.  It is impossible to properly nail the stud to the sole or plate if a significant portion of the stud is missing.

The manufacturers installation instructions for preservatively treated (PT) lumber have required hot-dipped galvanized fasteners for a number of years.  In practice, those requirements were largely ignored.  Starting circa-2002/2003, the EPA forced manufacturers to discontinue the use of arsenic-based chemical treatments.  This shift produced some unintended consequences.

The current generation of preservatively treated lumber uses either copper-based or borate-based chemical treatments.  The borate-based products are water-soluble and must not be exposed to weather.  The borate products are significantly less corrosive than copper-based materials.  The copper-based products constitute much of the preservatively treated lumber used.  Copper-based preservatively wood is highly corrosive.  Where preservatively treated lumber is used, it is critical that appropriate fasteners must be used.

Since the load is cumulative, the further down the load path you go – the higher the forces involved are.  The point of highest stress is generally at the connection between the wood framing and the concrete foundation.  Imagine the impact on a dwelling if the shear panels and cripple studs are nailed into a PT mudsill using improper fasteners.  In a short while, corrosion will compromise these critical connections.  We then have a dwelling that is essentially not secured to the foundation.  There are some indications that even hot-dipped galvanized may provide insufficient corrosion protection with the copper-based products.

In some multiple story building, double sole plates may be encountered.  The second sole plate may have been installed to act as a form for poured-in-place lightweight concrete or gypsum sub-floor material.  Where this occurs, it is important to maintain a load path through both plates.  In new construction, this is accomplished by nailing the first sole plate and second sole plate with a sufficient number of nails specified by a design professional.  In existing construction, it may be necessary to use extra long nails or screws through both plates so that the fastener has enough penetration into the framing member below.

Allen Insurance "The" Source for Home Inspector Insurance Since 1992

Connections At Sill Plates
Because shear loads are cumulative as they work their way down a building, they are greatest at the base of a building.  Shear loads are transferred from the shear wall into the foundation through the sill plate.  Consequently, the sill plate must be attached to the foundation with anchor bolts or side plates.  Before the load enters the anchor bolt or side plate, it must successfully pass through the sill plate.  Sill plates should be in good condition and free from cracks.  If a cracked or split plate is encountered, it should be replaced before proceeding with any retrofit.

In older construction the existing anchor bolts in the sill plate are usually smaller diameter bolts.  Washers may or may not be installed.  The bolts will generally be spaced much further apart than current requirements.  Older bolts may be degraded due to rust/corrosion.  Some older buildings pre-date the requirements for bolting of the sill plates to the concrete stem wall.  When retrofitting these older foundations, special retrofit anchors must be used to strengthen the sill plate to foundation connection.  Retrofit sill plate anchors are installed in two ways: drilled-in anchors through the sill plate or side plates that connect the sill plate to the foundation concrete or masonry.  Side plates are used when there is not enough room to stand a drill motor on top of the sill plate.

Anchor Bolt Spacing Requirements
A means to positively connect the structure to the foundation is required.  The size and spacing requirements for anchor bolts can vary with seismic design category, building height, etc.  In engineered designs, the registered design professional may specify bolting requirements that significantly exceed minimum requirements based on the design calculations.  The minimum requirement is that bolts be spaced no farther than 6’ apart.  Every section of the sill plate should have a minimum of two bolts.

Anchor Bolt & Washer Size
Per the CBC 2007, the minimum bolt diameter in Seismic Design Category (SDC) D is ½”.  In SDC E, 5/8” bolts are required.  Certain local jurisdictions may require the use 5/8” anchor bolts in all cases.  Some local jurisdictions may also require the use of hot-dipped galvanized anchor bolts where PT lumber sills are installed.  Where 5/8” bolts are installed, some local jurisdictions may allow the use of non- hot-dipped galvanized anchor bolts with PT sill plates.  Refer to the authority having jurisdiction for specific local requirements.

During the 1994 Northridge, CA earthquake, the sill plates secured with older style washers or no washers were found to split or pulled through the anchor bolts.  It was found that a square plate washer is far more effective in a creating good connection between the sill plate and the bolt.  They also make tightening of expansion anchors easier.

In SDC D & E 3”x3” plate washers are required. These washers are required to be a minimum of .229” thick – that is almost a ¼”. These washers may be slotted to allow for centering on the sill. When slotted washers are used, a standard cut washer must also be used on top.

Bolt Clearances To The Outside Edge Of The Foundation
Foundation bolts require a minimum edge distance in concrete.  Anchor bolts installed with insufficient distance to the outside edge of the foundation wall will fail in earthquakes or other high stress conditions.

When the foundation walls are located slightly out of position, contractors will sometimes “fudge” the wood wall location. They do this by partially overhanging the sill plate at the edge of the foundation wall. When such a condition is encountered, a registered design professional should be consulted. If the wall overhang is severe or the required edge distances are not provided, a special repair or connection may be needed to effectively transfer the shear loads.

Provide Proper Depth Of Embedment In The Concrete
To safely resist imposed loads, all anchors need a minimum 7” depth of embedment in the concrete. If an anchor is set too deep, it should be left in place and another anchor installed nearby. The plate washers and nuts should not be countersunk into the sill plate as this weakens the connection.

Installing Retrofit Anchors
As with new construction, retrofit foundation bolts require a minimum edge distance in concrete.  The manufacturer’s recommendations will specify the minimum edge distance required for each diameter anchor.  In retrofit installations, obstructions may require the hole be drilled at slight angle.  It is important that the bottom of the hole still has the minimum edge clearance distance.  This is particularly important when using mechanical anchors.

Drilled-in retrofit type anchors come in two basic types: mechanical and adhesive.  Adhesive anchors have the advantage of working in lower strength existing concrete.  They are more expensive to install than mechanical anchors and require greater quality control during installation.  Mechanical wedge anchors are easier to install but generally require greater concrete strength due to the concentration of stress at the expansion clip.  When sufficient concrete strength exits, either adhesive or mechanical anchors may be used.  Generally the strength of both anchor types in concrete is greater than their strength in the wood sill plate.  All anchoring products should be installed per the manufacturer’s installation instruction.  Always check with manufacturer and the local building official to determine if special inspection is required.

Normally, drilled-in anchors should be installed near the center of the sill plate.  This will furnish the minimum required 1-½ bolt diameter edge distance in the wood, For 2 x 6 sill plates, this will generally provide adequate edge distance in the concrete.  When edge distance permits, drilled-in anchors can be installed directly through the blocking added for cripple wall strengthening but longer anchors are needed to provide the minimum depth of embedment in the concrete.  Longer anchors may also be required when in older construction where the sill plates are actually a full 2” thick as opposed to the 1-5/8” actual thickness found in nominal lumber.

Installing Mechanical Retrofit Foundation Anchors
Mechanical anchors attach to the concrete through friction by mechanically expanding or “wedging” against the concrete.  This type of anchor is only effective if the concrete is in good shape and the required edge distance is maintained.  A proper diameter hole is essential to allow the anchor to properly engage.  Generally, the proper hole diameter is the nominal size of the anchor.  Sometimes the bolt may not engage properly due to air or powder pockets in the concrete at the bolts expansion wedge.  This will be apparent when the bolt cannot be torqued to the required strength.  Should this occur, the bolt should be abandoned.  A new bolt should be installed nearby in a new hole.

Wedge anchors must be properly torqued per the manufacturers requirements to properly set them in concrete. For sill plate anchors, the range is generally 50-120 ft-lbs. Under-torquing a bolt can result in pullout under stress. Over-torquing the bolt can result in compression/damage to the wood sill plate under the washer. Always follow the manufacturer’s recommendation for the required torque and use a calibrated torque wrench.

Installing Adhesive Retrofit Foundation Anchors
CAREFULLY CLEAN THE HOLE
Unlike mechanical anchors, adhesive anchors attach to the concrete chemically; they are glued to the concrete.  These products usually come in a two-part tube applicator and are readily available.  Because the product creates a chemical bond between the anchor rod and the concrete, it is extremely important that the hole be properly drilled and cleaned.  This product must adhere directly to the concrete surface.  Any residual concrete dust that might be left in the hole after drilling may result in a failed connection.  Carefully clean the hole as required by the manufacturer.  The hole must be properly brushed and blown out prior to adhesive installation.

The manufacturer’s recommendation will show the minimum embedment depths required.  When holes are drilled deeper than required, nuts and plate washers should be installed on the mechanical and adhesive anchors before the pass through the sill plate.  This will prevent the anchor from sinking too deep into the hole.  The adhesives used are expensive.  Consistently drilling holes deeper than necessary will result in higher than necessary material costs.

USE ALL-THREADED ROD
Although these products chemically bond to concrete they will NOT chemically bond to the anchor rod (steel).  Therefore, threaded rod is required for all adhesive-anchoring systems.  This allows the product to engage the threads and create a good mechanical bond to the rod.

COMPLETELY FILL THE HOLE IN THE SILL PLATE WITH ADHESIVE
Most adhesive products require holes in the concrete that are oversized 1/8 inch larger than the all-thread rod diameter.  This creates oversized holes in the wood sill.  To remedy this, enough adhesive should be placed in the hole to overflow the sill plate once the rod is installed.  This will allow the sill plate to immediately engage the anchor rod during an earthquake and allow it to transfer shear forces directly into the rod, thus reducing the chances of the sill plate splitting.

INSTALL ALL-THREAD ROD WITH THE PLATE WASHER AND NUT ATTACHED
The washer and nut should be placed on the rod prior to installing the rod since the adhesive extruding from the top of the sill plate will make it difficult, if not impossible to install the washer and nut at a later time.

WAIT UNTIL FULLY CURED BEFORE TIGHTENING
Adhesive anchor installations will need to cure for several hours before they can be tested.  Always check manufacturer’s requirements for minimum set and cure time.  The time will vary depending on the product used and the temperature.

FOLLOW SAFETY REQUIREMENTS
A final word of caution on the use of adhesive anchors: you need to protect workers and the people living in the building from the fumes. Check with the manufacturer to find out which product is appropriate for the use and what precautions will be needed.

Installing Side Plates
When installing these plates, follow the manufacturer’s installation instructions carefully. Unless otherwise approved. Lag screws require pre-drilling to avoid splitting the sill plate during seismic loading. Pre-drilling for lag screws is required even with pneumatic or electric wrenches. Care should be taken to not over tighten the lag screws during installation. This will “strip” out the hole. To prevent damage to the hole, never drive the lag screws with a hammer.

Lag screws require two different diameter pre-drill holes.  The larger diameter pre-drilled hole is for the solid shank portion of the screw.  This hole should be drilled the diameter as the screw itself.  The second hole is the pre-drill hole for the threaded portion.  This hole must be smaller than the threaded diameter in order for the lag screw to grip the wood.

Retrofit Interior Post To Girder Connections
When seismic retrofitting has been performed, the post connections should include toenail connections.  The addition of straps or clips may be necessary when there is no existing connection.  Post and column connections need to be sufficient to resist lateral forces and any uplift forces.  In general, in an older dwelling the biggest performance improvements will be seen by upgrading the perimeter foundation connections and properly bracing any cripple walls or soft first stories.  By themselves, elaborate upgrades to interior post connection will provide only a limited benefit.  Generally, the post to beam/girder connections need to be sufficient to resist any lateral forces imposed as well as any uplift forces.  Generally, toenail connections at the top and bottom will keep the posts from shifting during an earthquake.

Submitted by: Skip Walker
Skip Walker lives in the SF Bay Area and has performed about 2,000 paid inspections since becoming a CREIA member in 2003. Skip is both a CREIA Master Inspector and an ASHI Certified Inspector. Skip is an ICC Certified Residential Combination Building Inspector and a F.I.R.E. Certified Inspector. Skip is the education chair for the Silicon Valley ASHI/CREIA Chapter. He also holds a California Real Estate Appraisal Trainee License.


Click here to learn about OREP Home Inspector E&O Insusrance


Take Your Business to the Next Level! Call TWI Affiliates Training


COA - Casey, O'Malley Associates - The Right Direction


« 1 | 2 | 3 | 4 »

Page 3



EVENTS &
EDUCATION

Click here to go to the CREIA Meeting and Events Calendar


Congratulations!

New Candidates

Paula Martin
Lane Aebi
Rick Dehlinger
Stephen Miller
Paul Stream
David Davis
Gary Gramling
Mike Grafton

New CCIs

Brian Dwight

Visit Ask.CREIA.org


 

 
The CREIA Inspector eNewsThe CREIA Inspector eNewsThe CREIA Inspector eNews
August 2009 | Archives

Page « 1 | 2 | 3 | 4 »


Technical Article
Foundation Framing Connections

Proper connections between the framing of a dwelling and the foundation system are critical.  These connections provide the path to transfer building live and dead loads down through the structure to the foundation system where it is dispersed into the soil.  The further down the load path you go – the higher the stress on the connections.  Baring wood decay or other issues, wood-framing members themselves rarely fail.  It is the connections that fail when exposed to high stress conditions.  In California, we generally call those “earthquakes.”

Framing Connections Are Critical
Most of California falls into Seismic Design Category D.  A small part of California in the central valley/Modesto area falls into Seismic Design Category C.  For Seismic Design Categories D & E, the CBC 2007 requires that positive connections and anchorage be installed between the foundation and the framing system.  The installed connections must be sufficient to resist the design loads.  When earthquake lateral design forces exceed 150 pounds per foot, the toenail capacity is not taken into account in the load calculations.  In that case, additional means must be provided to insure proper load transfer.  This would generally be some sort of structural metal connector, etc.

Where the framing members are not continuous from foundation sill to roof, the members must be properly secured to insure a continuous load path.  Metal fasteners or straps may be required to be installed to insure a continuous load path.

At the bottom of a braced or shear wall, the attachment of the plate and the floor decking to the floor framing provides the load and shear transfer from the wall and the floor diaphragm to the floor framing below.  When nails or lag screws resist shear, they must be sufficiently long enough to penetrate through the sole plate and floor sheathing into the framing member below.

The fastening requirements for wood framed construction are found in CBC 2007 Table 2304.9.1.  For full load values, the CBC specifies a minimum fastener penetration into the framing member.  When the minimum fastener penetration falls below the values specified in the relevant table, the fastener cannot be taken into consideration when calculating the load capacity of the system.

The CBC requires that all wood studs have full bearing on the sill or plate.  While notching a stud over a foundation bolt is a common practice, it is improper.  It is impossible to properly nail the stud to the sole or plate if a significant portion of the stud is missing.

The manufacturers installation instructions for preservatively treated (PT) lumber have required hot-dipped galvanized fasteners for a number of years.  In practice, those requirements were largely ignored.  Starting circa-2002/2003, the EPA forced manufacturers to discontinue the use of arsenic-based chemical treatments.  This shift produced some unintended consequences.

The current generation of preservatively treated lumber uses either copper-based or borate-based chemical treatments.  The borate-based products are water-soluble and must not be exposed to weather.  The borate products are significantly less corrosive than copper-based materials.  The copper-based products constitute much of the preservatively treated lumber used.  Copper-based preservatively wood is highly corrosive.  Where preservatively treated lumber is used, it is critical that appropriate fasteners must be used.

Since the load is cumulative, the further down the load path you go – the higher the forces involved are.  The point of highest stress is generally at the connection between the wood framing and the concrete foundation.  Imagine the impact on a dwelling if the shear panels and cripple studs are nailed into a PT mudsill using improper fasteners.  In a short while, corrosion will compromise these critical connections.  We then have a dwelling that is essentially not secured to the foundation.  There are some indications that even hot-dipped galvanized may provide insufficient corrosion protection with the copper-based products.

In some multiple story building, double sole plates may be encountered.  The second sole plate may have been installed to act as a form for poured-in-place lightweight concrete or gypsum sub-floor material.  Where this occurs, it is important to maintain a load path through both plates.  In new construction, this is accomplished by nailing the first sole plate and second sole plate with a sufficient number of nails specified by a design professional.  In existing construction, it may be necessary to use extra long nails or screws through both plates so that the fastener has enough penetration into the framing member below.

Allen Insurance "The" Source for Home Inspector Insurance Since 1992

Connections At Sill Plates
Because shear loads are cumulative as they work their way down a building, they are greatest at the base of a building.  Shear loads are transferred from the shear wall into the foundation through the sill plate.  Consequently, the sill plate must be attached to the foundation with anchor bolts or side plates.  Before the load enters the anchor bolt or side plate, it must successfully pass through the sill plate.  Sill plates should be in good condition and free from cracks.  If a cracked or split plate is encountered, it should be replaced before proceeding with any retrofit.

In older construction the existing anchor bolts in the sill plate are usually smaller diameter bolts.  Washers may or may not be installed.  The bolts will generally be spaced much further apart than current requirements.  Older bolts may be degraded due to rust/corrosion.  Some older buildings pre-date the requirements for bolting of the sill plates to the concrete stem wall.  When retrofitting these older foundations, special retrofit anchors must be used to strengthen the sill plate to foundation connection.  Retrofit sill plate anchors are installed in two ways: drilled-in anchors through the sill plate or side plates that connect the sill plate to the foundation concrete or masonry.  Side plates are used when there is not enough room to stand a drill motor on top of the sill plate.

Anchor Bolt Spacing Requirements
A means to positively connect the structure to the foundation is required.  The size and spacing requirements for anchor bolts can vary with seismic design category, building height, etc.  In engineered designs, the registered design professional may specify bolting requirements that significantly exceed minimum requirements based on the design calculations.  The minimum requirement is that bolts be spaced no farther than 6’ apart.  Every section of the sill plate should have a minimum of two bolts.

Anchor Bolt & Washer Size
Per the CBC 2007, the minimum bolt diameter in Seismic Design Category (SDC) D is ½”.  In SDC E, 5/8” bolts are required.  Certain local jurisdictions may require the use 5/8” anchor bolts in all cases.  Some local jurisdictions may also require the use of hot-dipped galvanized anchor bolts where PT lumber sills are installed.  Where 5/8” bolts are installed, some local jurisdictions may allow the use of non- hot-dipped galvanized anchor bolts with PT sill plates.  Refer to the authority having jurisdiction for specific local requirements.

During the 1994 Northridge, CA earthquake, the sill plates secured with older style washers or no washers were found to split or pulled through the anchor bolts.  It was found that a square plate washer is far more effective in a creating good connection between the sill plate and the bolt.  They also make tightening of expansion anchors easier.

In SDC D & E 3”x3” plate washers are required. These washers are required to be a minimum of .229” thick – that is almost a ¼”. These washers may be slotted to allow for centering on the sill. When slotted washers are used, a standard cut washer must also be used on top.

Bolt Clearances To The Outside Edge Of The Foundation
Foundation bolts require a minimum edge distance in concrete.  Anchor bolts installed with insufficient distance to the outside edge of the foundation wall will fail in earthquakes or other high stress conditions.

When the foundation walls are located slightly out of position, contractors will sometimes “fudge” the wood wall location. They do this by partially overhanging the sill plate at the edge of the foundation wall. When such a condition is encountered, a registered design professional should be consulted. If the wall overhang is severe or the required edge distances are not provided, a special repair or connection may be needed to effectively transfer the shear loads.

Provide Proper Depth Of Embedment In The Concrete
To safely resist imposed loads, all anchors need a minimum 7” depth of embedment in the concrete. If an anchor is set too deep, it should be left in place and another anchor installed nearby. The plate washers and nuts should not be countersunk into the sill plate as this weakens the connection.

Installing Retrofit Anchors
As with new construction, retrofit foundation bolts require a minimum edge distance in concrete.  The manufacturer’s recommendations will specify the minimum edge distance required for each diameter anchor.  In retrofit installations, obstructions may require the hole be drilled at slight angle.  It is important that the bottom of the hole still has the minimum edge clearance distance.  This is particularly important when using mechanical anchors.

Drilled-in retrofit type anchors come in two basic types: mechanical and adhesive.  Adhesive anchors have the advantage of working in lower strength existing concrete.  They are more expensive to install than mechanical anchors and require greater quality control during installation.  Mechanical wedge anchors are easier to install but generally require greater concrete strength due to the concentration of stress at the expansion clip.  When sufficient concrete strength exits, either adhesive or mechanical anchors may be used.  Generally the strength of both anchor types in concrete is greater than their strength in the wood sill plate.  All anchoring products should be installed per the manufacturer’s installation instruction.  Always check with manufacturer and the local building official to determine if special inspection is required.

Normally, drilled-in anchors should be installed near the center of the sill plate.  This will furnish the minimum required 1-½ bolt diameter edge distance in the wood, For 2 x 6 sill plates, this will generally provide adequate edge distance in the concrete.  When edge distance permits, drilled-in anchors can be installed directly through the blocking added for cripple wall strengthening but longer anchors are needed to provide the minimum depth of embedment in the concrete.  Longer anchors may also be required when in older construction where the sill plates are actually a full 2” thick as opposed to the 1-5/8” actual thickness found in nominal lumber.

Installing Mechanical Retrofit Foundation Anchors
Mechanical anchors attach to the concrete through friction by mechanically expanding or “wedging” against the concrete.  This type of anchor is only effective if the concrete is in good shape and the required edge distance is maintained.  A proper diameter hole is essential to allow the anchor to properly engage.  Generally, the proper hole diameter is the nominal size of the anchor.  Sometimes the bolt may not engage properly due to air or powder pockets in the concrete at the bolts expansion wedge.  This will be apparent when the bolt cannot be torqued to the required strength.  Should this occur, the bolt should be abandoned.  A new bolt should be installed nearby in a new hole.

Wedge anchors must be properly torqued per the manufacturers requirements to properly set them in concrete. For sill plate anchors, the range is generally 50-120 ft-lbs. Under-torquing a bolt can result in pullout under stress. Over-torquing the bolt can result in compression/damage to the wood sill plate under the washer. Always follow the manufacturer’s recommendation for the required torque and use a calibrated torque wrench.

Installing Adhesive Retrofit Foundation Anchors
CAREFULLY CLEAN THE HOLE
Unlike mechanical anchors, adhesive anchors attach to the concrete chemically; they are glued to the concrete.  These products usually come in a two-part tube applicator and are readily available.  Because the product creates a chemical bond between the anchor rod and the concrete, it is extremely important that the hole be properly drilled and cleaned.  This product must adhere directly to the concrete surface.  Any residual concrete dust that might be left in the hole after drilling may result in a failed connection.  Carefully clean the hole as required by the manufacturer.  The hole must be properly brushed and blown out prior to adhesive installation.

The manufacturer’s recommendation will show the minimum embedment depths required.  When holes are drilled deeper than required, nuts and plate washers should be installed on the mechanical and adhesive anchors before the pass through the sill plate.  This will prevent the anchor from sinking too deep into the hole.  The adhesives used are expensive.  Consistently drilling holes deeper than necessary will result in higher than necessary material costs.

USE ALL-THREADED ROD
Although these products chemically bond to concrete they will NOT chemically bond to the anchor rod (steel).  Therefore, threaded rod is required for all adhesive-anchoring systems.  This allows the product to engage the threads and create a good mechanical bond to the rod.

COMPLETELY FILL THE HOLE IN THE SILL PLATE WITH ADHESIVE
Most adhesive products require holes in the concrete that are oversized 1/8 inch larger than the all-thread rod diameter.  This creates oversized holes in the wood sill.  To remedy this, enough adhesive should be placed in the hole to overflow the sill plate once the rod is installed.  This will allow the sill plate to immediately engage the anchor rod during an earthquake and allow it to transfer shear forces directly into the rod, thus reducing the chances of the sill plate splitting.

INSTALL ALL-THREAD ROD WITH THE PLATE WASHER AND NUT ATTACHED
The washer and nut should be placed on the rod prior to installing the rod since the adhesive extruding from the top of the sill plate will make it difficult, if not impossible to install the washer and nut at a later time.

WAIT UNTIL FULLY CURED BEFORE TIGHTENING
Adhesive anchor installations will need to cure for several hours before they can be tested.  Always check manufacturer’s requirements for minimum set and cure time.  The time will vary depending on the product used and the temperature.

FOLLOW SAFETY REQUIREMENTS
A final word of caution on the use of adhesive anchors: you need to protect workers and the people living in the building from the fumes. Check with the manufacturer to find out which product is appropriate for the use and what precautions will be needed.

Installing Side Plates
When installing these plates, follow the manufacturer’s installation instructions carefully. Unless otherwise approved. Lag screws require pre-drilling to avoid splitting the sill plate during seismic loading. Pre-drilling for lag screws is required even with pneumatic or electric wrenches. Care should be taken to not over tighten the lag screws during installation. This will “strip” out the hole. To prevent damage to the hole, never drive the lag screws with a hammer.

Lag screws require two different diameter pre-drill holes.  The larger diameter pre-drilled hole is for the solid shank portion of the screw.  This hole should be drilled the diameter as the screw itself.  The second hole is the pre-drill hole for the threaded portion.  This hole must be smaller than the threaded diameter in order for the lag screw to grip the wood.

Retrofit Interior Post To Girder Connections
When seismic retrofitting has been performed, the post connections should include toenail connections.  The addition of straps or clips may be necessary when there is no existing connection.  Post and column connections need to be sufficient to resist lateral forces and any uplift forces.  In general, in an older dwelling the biggest performance improvements will be seen by upgrading the perimeter foundation connections and properly bracing any cripple walls or soft first stories.  By themselves, elaborate upgrades to interior post connection will provide only a limited benefit.  Generally, the post to beam/girder connections need to be sufficient to resist any lateral forces imposed as well as any uplift forces.  Generally, toenail connections at the top and bottom will keep the posts from shifting during an earthquake.

Submitted by: Skip Walker
Skip Walker lives in the SF Bay Area and has performed about 2,000 paid inspections since becoming a CREIA member in 2003. Skip is both a CREIA Master Inspector and an ASHI Certified Inspector. Skip is an ICC Certified Residential Combination Building Inspector and a F.I.R.E. Certified Inspector. Skip is the education chair for the Silicon Valley ASHI/CREIA Chapter. He also holds a California Real Estate Appraisal Trainee License.


Click here to learn about OREP Home Inspector E&O Insusrance


Take Your Business to the Next Level! Call TWI Affiliates Training


COA - Casey, O'Malley Associates - The Right Direction


« 1 | 2 | 3 | 4 »

Page 3



EVENTS &
EDUCATION

Click here to go to the CREIA Meeting and Events Calendar


Congratulations!

New Candidates

Paula Martin
Lane Aebi
Rick Dehlinger
Stephen Miller
Paul Stream
David Davis
Gary Gramling
Mike Grafton

New CCIs

Brian Dwight

Visit Ask.CREIA.org


 

 

The CREIA Inspector eNewsThe CREIA Inspector eNewsThe CREIA Inspector eNews
August 2009 | Archives

Page « 1 | 2 | 3 | 4 »


InspectTest

This series of columns is designed to familiarize CREIA members with “The Glossary Project” which is “Standardized Terminology for the Professional Real Estate Inspector”. This is a must have for all inspectors and is especially helpful in preparing the candidate for the CREIA CCI test as most of the terms in the test are defined in The Glossary Project. It is available from shop.CREIA.org.

  1. Devices, equipment or materials with a label, seal, symbol or other identifying mark of a testing laboratory, inspection agency or organization concerned with product evaluation that maintains periodic inspections of the production of the item and attests to compliance with a specific standard is referred to as being ___________________.
  2. ___________ __________ is an area, room or space normally occupied and being heated or cooled for human habitation by any equipment.
  3. An electrical circuit with two or more ungrounded conductors which share grounded conductors is a ________-________ ___________ _________.
  4. ____________ _______________ is the emptying of a plumbing fixture in a reasonable amount of time, without overflow when another fixture is drained simultaneously.
  5. A nonstructural facing of brick, concrete, stone, tile, metal, plastic or other similar material attached to a backing for the purpose of ornamentation, protection or insulation is known as ________________________.
  6. The ______________ ______________ is a device or devices by which the electrical system can be disconnected from its source of supply.
  7. A ___________ __________ is a device for lifting sewage by entraining it on a high-velocity jet stream, air, or water.
  8. The final thin layer in a three-coat system of hand finished plaster or stucco is the ____________ _____________.
  9. ___________ ___________ is the formed metal secured to a wall, curb or chimney to cover the upper edge of a base flashing for weatherproofing, typically at roofs and balconies.
  10. A chemical applied to wood to protect it from insects, dry rot, and moisture is a ___________________ ___________________.

Click here for the answers (Sorry members only)


Off The Net

Pool & Spa Safety... Don't read at your own peril.
Click here (Sorry T.I.E. Members only)


 

Allen Insurance "The" Source for Home Inspector Insurance Since 1992


CREIA Leadership and BOD Meetings in San Diego, CA, July 2009

July 2009 CREIA Leadership Day - Chapter Presidents

CREIA Chapter Presidents at the Leadership Day Meeting July 2009 San Diego, CA

 

July 2009 CREIA BOD Meeting

CREIA BOD Meeting July 2009 San Diego, CA

 

July 2009 CREIA BOD Meeting

CREIA BOD Meeting July 2009 San Diego, CA

 


Click here to learn about OREP Home Inspector E&O Insusrance


Take Your Business to the Next Level! Call TWI Affiliates Training


COA - Casey, O'Malley Associates - The Right Direction


 

« 1 | 2 | 3 | 4 »

Page 4



EVENTS &
EDUCATION

Click here to go to the CREIA Meeting and Events Calendar


Congratulations!

New Candidates

Paula Martin
Lane Aebi
Rick Dehlinger
Stephen Miller
Paul Stream
David Davis
Gary Gramling
Mike Grafton

New CCIs

Brian Dwight


Visit Ask.CREIA.org


 

 
The CREIA Inspector eNewsThe CREIA Inspector eNewsThe CREIA Inspector eNews
August 2009 | Archives

Page « 1 | 2 | 3 | 4 »


InspectTest

This series of columns is designed to familiarize CREIA members with “The Glossary Project” which is “Standardized Terminology for the Professional Real Estate Inspector”. This is a must have for all inspectors and is especially helpful in preparing the candidate for the CREIA CCI test as most of the terms in the test are defined in The Glossary Project. It is available from shop.CREIA.org.

  1. Devices, equipment or materials with a label, seal, symbol or other identifying mark of a testing laboratory, inspection agency or organization concerned with product evaluation that maintains periodic inspections of the production of the item and attests to compliance with a specific standard is referred to as being ___________________.
  2. ___________ __________ is an area, room or space normally occupied and being heated or cooled for human habitation by any equipment.
  3. An electrical circuit with two or more ungrounded conductors which share grounded conductors is a ________-________ ___________ _________.
  4. ____________ _______________ is the emptying of a plumbing fixture in a reasonable amount of time, without overflow when another fixture is drained simultaneously.
  5. A nonstructural facing of brick, concrete, stone, tile, metal, plastic or other similar material attached to a backing for the purpose of ornamentation, protection or insulation is known as ________________________.
  6. The ______________ ______________ is a device or devices by which the electrical system can be disconnected from its source of supply.
  7. A ___________ __________ is a device for lifting sewage by entraining it on a high-velocity jet stream, air, or water.
  8. The final thin layer in a three-coat system of hand finished plaster or stucco is the ____________ _____________.
  9. ___________ ___________ is the formed metal secured to a wall, curb or chimney to cover the upper edge of a base flashing for weatherproofing, typically at roofs and balconies.
  10. A chemical applied to wood to protect it from insects, dry rot, and moisture is a ___________________ ___________________.

Click here for the answers (Sorry members only)


Off The Net

Pool & Spa Safety... Don't read at your own peril.
Click here (Sorry T.I.E. Members only)


 

Allen Insurance "The" Source for Home Inspector Insurance Since 1992


CREIA Leadership and BOD Meetings in San Diego, CA, July 2009

July 2009 CREIA Leadership Day - Chapter Presidents

CREIA Chapter Presidents at the Leadership Day Meeting July 2009 San Diego, CA

 

July 2009 CREIA BOD Meeting

CREIA BOD Meeting July 2009 San Diego, CA

 

July 2009 CREIA BOD Meeting

CREIA BOD Meeting July 2009 San Diego, CA

 


Click here to learn about OREP Home Inspector E&O Insusrance


Take Your Business to the Next Level! Call TWI Affiliates Training


COA - Casey, O'Malley Associates - The Right Direction


 

« 1 | 2 | 3 | 4 »

Page 4



EVENTS &
EDUCATION

Click here to go to the CREIA Meeting and Events Calendar


Congratulations!

New Candidates

Paula Martin
Lane Aebi
Rick Dehlinger
Stephen Miller
Paul Stream
David Davis
Gary Gramling
Mike Grafton

New CCIs

Brian Dwight


Visit Ask.CREIA.org


 

 
 

Inspector Login

Website Hosted by Home Inspector Pro